6.4.4 Object and Data Types Supported

Data types supported

Data type

Short name

Description

3

I2

Integer 16

4

I4

Integer 32

5

-

Unsigned 8

6

O2

Unsigned 16

7

O4

Unsigned 32

9

-

Visible string

10

-

Byte string

33

N2

Standardized value (16 bit)

35

V2

Bit sequence

54

-

Time difference without date indication

6.4.5 Standardized Value

The frequency reference value is transmitted to the frequency converter in the form of a 16-bit word. The value is transmitted in integers (0-32767). The value
16384 (4000 Hex) corresponds to 100%. Negative numbers are formed with the aid of the twos complement.

0% = 0 (0h), 100% is 2

14

(4000h)

Data type

N2

Range

-200%...+200%

Resolution

2

-14

= 0.0061%

Length

2 bytes

Notation: 2s complement notation.
MSB is 1st bit after sign bit in 1st byte.
Sign bit = 0 = positive number
Sign bit = 1 = negative number

Bit

8

7

6

5

4

3

2

1

Byte 1

SIGN

2

14

2

13

2

12

2

11

2

10

2

9

2

Byte 2

2

7

2

6

2

5

24

2

3

2

2

2

1

2

0

Bit sequence
16 boolean values for control and presentation of user functions.

Notation is binary

Bit

8

7

6

5

4

3

2

1

Byte 1

15

14

13

12

11

10

9

8

Byte 2

7

6

5

4

3

2

1

0