5 alarm and warning words – GE Industrial Solutions AF-600 FP Profibus DP User Manual

Page 80

Advertising
background image

8.2.5 Alarm and Warning Words

Alarm word, Warning word and PROFIBUS warning word are shown on the display in Hex format. If there is more than one warning or alarm, a sum of all warnings
or alarms will be shown. Alarm word, warning word and PROFIBUS warning word can also be displayed using the serial network in par. DR-90 Alarm Word, par.
DR-92 Warning Word and par. PB-53 Profibus Warning Word.

AF-650 GP & AF-600 FP

Bit (Hex)

Unit diag-
nose bit

Alarm word (par.
DR-90 Alarm Word)

Alarm no.

00000001

48

Brake check

28

00000002

49

Power card over temper-
ature

29

00000004

50

Earth fault

14

00000008

51

Control card over tem-
perature

65

00000010

52

Control word timeout

18

00000020

53

Over current

13

00000040

54

Torque limit

12

00000080

55

Motor thermistor over
temp.

11

00000100

40

Motor Electronic Over-
load over temperature

10

00000200

41

Drive overloaded

9

00000400

42

DC link under voltage

8

00000800

43

DC link over voltage

7

00001000

44

Short circuit

16

00002000

45

Inrush fault

33

00004000

46

Mains phase loss

4

00008000

47

Auto Tune not OK

50

00010000

32

Live zero error

2

00020000

33

Internal fault

38

00040000

34

Brake overload

26

00080000

35

Motor phase U is missing

30

00100000

36

Motor phase V is missing

31

00200000

37

Motor phase W is missing

32

00400000

38

Network comm. fault

34

00800000

39

24 V supply fault

47

01000000

24

Mains failure

36

02000000

25

1.8 V supply fault

48

04000000

26

Brake resistor short cir-
cuit

25

08000000

27

Brake chopper fault

27

10000000

28

Option change

67

20000000

29

Drive Initialized

80

40000000

30

Safe stop

68

80000000

31

Mechanical brake low

63

AF-650 GP & AF-600 FP

Bit (Hex)

Unit diag-
nose bit

Warning word (par.
DR-92 Warning Word)

Alarm no.

00000001

112

Brake check

28

00000002

113

Power card over temper-
ature

29

00000004

114

Earth fault

14

00000008

115

Control card

65

00000010

116

Control word timeout

18

00000020

117

Over current

13

00000040

118

Torque limit

12

00000080

119

Motor thermistor over
temp.

11

00000100

104

Motor Electronic Overload
over temperature

10

00000200

105

Drive overloaded

9

00000400

106

DC link under voltage

8

00000800

107

DC link over voltage

7

00001000

108

DC link voltage low

6

00002000

109

DC link voltage high

5

00004000

110

Mains phase loss

4

00008000

111

No motor

3

00010000

96

Live zero error

2

00020000

97

10 V low

1

00040000

98

Brake overload

26

00080000

99

Brake resistor short circuit

25

00100000

100

Brake chopper fault

27

00200000

101

Speed limit

49

00400000

102

Network comm. fault

34

00800000

103

24 V supply fault

47

01000000

88

Mains failure

36

02000000

89

Current limit

59

04000000

90

Low temperature

66

08000000

91

Voltage limit

64

10000000

92

Encoder loss

61

20000000

93

Output frequency limit

62

40000000

94

Unused

-

80000000

95

Warning word 2 (ext. stat.
word)

-

AF-650 GP & AF-600 FP

Bit (Hex)

Unit diag-
nose bit

PROFIBUS warning word (par. PB-53 Pro-
fibus Warning Word
)

00000001

160

Connection with DP-master is not ok

00000002

161

Unused

00000004

162

NDL (Network Data link Layer) is not ok

00000008

163

Clear data command received

00000010

164

Actual value is not updated

00000020

165

Baudrate search

00000040

166

PROFIBUS ASIC is not transmitting

00000080

167

Initialising of PROFIBUS is not ok

00000100

152

Drive is tripped

00000200

153

Internal CAN error

00000400

154

Wrong configuration data from PLC

00000800

155

Wrong ID sent by PLC

00001000

156

Internal error occurred

00002000

157

Not configured

00004000

158

Timeout active

00008000

159

Warning 34 active

AF-650 GP/AF-600 FP Profibus DP Operating Instructions

79

8

Advertising