Depending on the setting of par. F-50 Reference Range the reference and MAV are scaled accordingly:

NB!
If par. F-50 Reference Range is set to [0] Min - Max, a negative reference will be handled as 0%.

The actual output of the frequency converter is limited by the speed limit parameters Motor Low/High Speed Limit [RPM/Hz] in par. F-18 Motor Speed Low Limit
[RPM]
to par. F-15 Motor Speed High Limit [Hz].
The final speed limit is set by par. F-03 Max Output Frequency 1.

The reference and the MAV have the format which appears from the table

MRV / MAV

Integer in hex

Integer in decimal

100%

4000

16.384

75%

3000

12.288

50%

2000

8.192

25%

1000

4.096

0%

0

0

-25%

F000

-4.096

-50%

E000

-8.192

-75%

D000

-12.288

-100%

C000

-16.384

NB!
Negative numbers are formed as two's complement.

NB!
The data type for MRV and MAV is a N2 16 bit standardised value, meaning it can express a range from -200% to +200% (8001 to 7FFF).

AF-650 GP/AF-600 FP Profibus DP Operating Instructions