4.5 GE Drive Control Profile

4.5.1 Control Word according to Drive Profile (CTW)

To select GE Drive protocol in the control word, par. O-10 Control Word Profile must be set to GE Drive protocol [0]. The control word is used to send commands
from a master (PLC or PC) to a slave (frequency converter).

Please refer to Application Examples for an example of a control word message using PPO type 3.

Bit

Bit value = 0

Bit value = 1

00

Reference value

external selection lsb

01

Reference value

external selection msb

02

DC brake

Accel/Decel

03

Coasting

No coasting

04

Quick stop

Accel/Decel

05

Hold output frequency

Use Accel/Decel

06

Accel/Decel stop

Start

07

No function

Reset

08

No function

Jog

09

Ramp 1

Accel/Decel 2

10

Data invalid

Data valid

11

No function

Relay 01 active

12

No function

Relay 04 active

13

Parameter set-up

selection lsb

14

Parameter set-up

selection msb

15

No function

Reverse

Explanation of the Control Bits

Bits 00/01 Reference value
Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in par. C-05 Multi-step Frequency 1 - 8 according to the following
table:

NB!
In par. O-56 Preset Reference Select a selection is made to define how Bit 00/01 gates with the corresponding function on the digital inputs.

Programmed

ref. value

Parameter

Bit 01

Bit 00

1

C-05 [0]

0

0

2

C-05 [1]

0

1

3

C-05 [2]

1

0

4

C-05 [3]

1

1

Bit 02, DC brake
Bit 02 = 0 leads to DC braking and stop. Braking current and duration are set in par. B-01 DC Brake Current and par. B-02 DC Braking Time. Bit 02 = 1 leads to
ramping.

Bit 03, Coasting
Bit 03 = 0 causes the frequency converter to immediately "let go" of the motor (the output transistors are "shut off"), so that it coasts to a standstill.
Bit 03 = 1 enables the frequency converter to start the motor if the other starting conditions have been fulfilled.

AF-650 GP/AF-600 FP Profibus DP Operating Instructions