When the parameter request is invalid, the frequency converter will return a corresponding error code. The table below lists the full range of error codes.

Error codes for DP V1 parameter requests

Error code

Meaning

Additional Info

0x00

Unknown parameter

0

0x01

Parameter is read-only

sub-index

0x02

Value out of range due to max/min value

sub-index

0x03

Wrong sub-index

sub-index

0x04

Parameter is no array

0

0x05

Wrong data type (wrong data length)

0

0x06

This parameter may not be set, only reset

sub-index

0x07

Descriptive element is read-only

sub-index

0x09

No description available (only value)

0

0x0b

Process control not possible

0

0x0f

No text array available (only value)

0

0x11

Not possible in current state

0

0x14

Value out of range due to drive state/configuration

sub-index

0x15

Reply too long (more than 240 bytes)

0

0x16

Wrong parameter address (unknown or unsupported value for attribute, element, par. number or sub-
index or illegal combination)

0

0x17

Illegal format (for writing)

0

0x18

Value amount not consistent

0

0x65

Wrong axis: action not possible with this axis

-

0x66

Unknown service request

-

0x67

This service is not possible with multi parameter access

-

0x68

Parameter value can not be read from network

-