4.4 PROFIdrive Control Profile

4.4.1 PROFIdrive Control Profile

This section describes the functionality of the control word and status word in the PROFIdrive profile. Select this profile by setting par. O-10 Control Word Profile.

4.4.2 Control Word according to PROFIdrive Profile (CTW)

The Control word is used to send commands from a master (e.g. a PC) to a
slave.

Bit

Bit = 0

Bit = 1

00

OFF 1

ON 1

01

OFF 2

ON 2

02

OFF 3

ON 3

03

Coasting

No coasting

04

Quick stop

Accel/Decel

05

Hold frequency output

Use Accel/Decel

06

Accel/Decel stop

Start

07

No function

Reset

08

Jog 1 OFF

Jog 1 ON

09

Jog 2 OFF

Jog 2 ON

10

Data invalid

Data valid

11

No function

Slow down

12

No function

Catch up

13

Parameter set-up

Selection lsb

14

Parameter set-up

Selection msb

15

No function

Reverse

Explanation of the Control Bits

Bit 00, OFF 1/ON 1
Normal ramp stop using the ramp times of the actual selected ramp.
Bit 00 = "0" leads to the stop and activation of the output relay 1 or 2 if the output frequency is 0 Hz and if [Relay 123] has been selected in par. E-24 Function
Relay
.
When bit 00 = "1", the frequency converter is in State 1: “Switching on inhibited”.
Please refer to the PROFIdrive State Transition Diagram, at the end of this section.

Bit 01, OFF 2/ON 2
Coasting stop
When bit 01 = "0", a coasting stop and activation of the output relay 1 or 2 occurs if the output frequency is 0 Hz and if [Relay 123] has been selected in par.
E-24 Function Relay.
When bit 01 = "1", the frequency converter is in State 1: “Switching on inhibited”. Please refer to the PROFIdrive State Transition Diagram, at the end of this section.

Bit 02, OFF 3/ON 3
Quick stop using the ramp time of par. C-23 Quick Stop Decel Time. When bit 02 = "0", a quick stop and activation of the output relay 1 or 2 occurs if the output
frequency is 0 Hz and if [Relay 123] has been selected in par. E-24 Function Relay.
When bit 02 = "1", the frequency converter is in State 1: “Switching on inhibited”.
Please refer to the PROFIdrive State Transition Diagram, at the end of this section.

Bit 03, Coasting/No coasting
Coasting stop Bit 03 = "0" leads to a stop. When bit 03 = "1", the frequency converter can start if the other start conditions are satisfied.

NB!
The selection in par. O-50 Coasting Select Coasting select determines how bit 03 is linked with the corresponding function of the digital inputs.

AF-650 GP/AF-600 FP Profibus DP Operating Instructions