14 number of parameters, 15 attribute, 16 attribute value (10h) – GE Industrial Solutions AF-600 FP Profibus DP User Manual

Page 47: 17 attribute description (20h)

Advertising
background image

5.2.14 Number of Parameters

For multi-parameter requests specifying the number of the Parameter Address and/or Parameter Value areas. For a single request the number is 1.

5.2.15 Attribute

The attribute determines which kind of data to access. The frequency converter will respond to the attributes Value (10H), Description (20H) and Text (30H).

5.2.16 Attribute Value (10H)

The attribute value permits reading or writing of parameter values.

5.2.17 Attribute Description (20H)

The attribute description permits access to the parameter description. It is possible to read out one single description element, or all elements for one parameter
in one message. The table below provides an overview of the existing Parameter Description, which exists for each parameter in the frequency converter.

Parameter description elements (all elements are read-only):

Sub-index

Meaning

Data Type

1

Identifier ID

V2

2

Number of array elements or length or string

U16

3

Standardization factor

float

4

Variable attribute

Octet string 2

5

Reserved

Octet string 4

6

Name

Visible string 16

7

Lower limit

Octet string 4

8

Upper limit

Octet string 4

9

Reserved

Octet string 2

10

ID extension

V2

11

PCD reference parameter

U16

12

PCD normalization

V2

0

Complete description

Octet string 46

In the following each description element is explained.

Identifier ID

Additional characteristics of a parameter.

Bit

Meaning

15

Reserved

14

Array

13

Parameter value can be reset only

12

Parameter has been changed from factory setting

11

Reserved

10

Additional text array available

9

Parameter is read-only

8

Standardizaton factor and variable attribute not relevant

0-7

Data type

Number of Array Elements