7.2 E.g.: Control Word Network using PPO Type

This example shows how the control word network relates to the PLC and the frequency converter, using Ge Drive Control Profile.

The control word network is sent from the PLC to the frequency converter. PPO Type 3 is used in the example in order to demonstrate the full range of modules.
All the values shown are arbitrary, and are provided for the purposes of demonstration only.

PCV

PCD

1

2

3

4

5

6

PCA

IND

PVA

CTW

MRV

PCD

PCD

PCD

PCD

04

7C

20

00

PQW:

256

258

260

262

264

266

268

270

272

274

master slave

CTW

MRV

Bit no.:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

1

0

0

0

1

1

1

1

1

0

0

0

4

7

C

The table above indicates the bits contained within the control word, and how they are presented as process data in PPO type 3for this example.

The following table indicates which bit functions, and which corresponding bit values are active for this example.

Bit

Bit value = 0

Bit value = 1

Bit value

00

Reference value

External selection lsb

0

C

01

Reference value

External selection msb

0

02

DC brake

Accel/Decel

1

03

Coasting

Enable

1

04

Quick stop

Accel/Decel

1

7

05

Freeze output

Accel/Decel enable

1

06

Accel/Decel stop

Start

1

07

No function

Reset

0

08

No function

Jog

0

4

09

Accel/Decel 1

Accel/Decel 2

0

10

Data not valid

Valid

1

11

No function

Relay 01 active

0

12

No function

Relay 02 active

0

0

13

Parameter set-up

Selection lsb

0

14

Parameter set-up

Selection msb

0

15

No function

Reversing

0

Function active

Function inactive

AF-650 GP/AF-600 FP Profibus DP Operating Instructions