3 pcv parameter access, 1 pca handling, 2 pca - parameter characteristics – GE Industrial Solutions AF-600 FP Profibus DP User Manual

Page 51

Advertising
background image

5.3 PCV Parameter Access

Parameter access via the PCV channel is performed by the PROFIBUS DP V0 cyclical data exchange, where the PCV channel is part of the PPOs described in the
chapter How to Control the Frequency Converter.


PCV

PCD

1

2

3

4

5

6

7

8

9

10

PCA

IND

PVA

CTW

MRV

PCD

PCD

PCD

PCD

PCD

PCD

PCD

PCD

STW

MAV

Byte
no.

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Type 1:

Type 2:

Type 5:

PCV:

Parameter Characteristics Value

PCD:

Process Data

PCA:

Parameter Characteristics (Bytes 1, 2)

IND:

Sub index (Byte 3. Byte 4 is not used)

PVA:

Parameter value (Bytes 5 to 8)

CTW:

Control word

STW:

Status word

MRV:

Main reference value

MAV:

Main actual value (Actual output frequency)

Using the PCV channel it is possible to read and write parameter values, as well as readout of a number of describing attributes of each parameter.

5.3.1 PCA Handling

The PCA part of PPO types 1, 2 and 5 can handle several tasks. The master can control and supervise parameters and request a response from the slave, whereas
the slave can respond to a request from the master.
Requests and responses is a handshake procedure and cannot be batched, meaning that if the master sends out a read/write request, it has to wait for the
response, before it sends a new request. The request or response data value will be limited to maximum 4 bytes, which implies that text strings are not transferable.
For further information, please see the Application Examples chapter.

5.3.2 PCA - Parameter Characteristics

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

RC

SMP

PNU

RC: Request/response characteristics (Range 0..15)
SMP: Spontaneous Messag (Not supported)
PNU : Parameter no. (Range 1..1999)

AF-650 GP/AF-600 FP Profibus DP Operating Instructions