The function is only possible if Multi Set-up has been chosen in par. K-10 Active
Set-up
. The selection in par. O-55 Set-up Select determines how bits 13 and
14 are linked with the corresponding function of the digital inputs. Changing
set-up while running is only possible if the set-ups have been linked in par.
K-12 This Set-up Linked to.

Set-up

Bit 13

Bit 14

1

0

0

2

1

0

3

0

1

4

1

1

Bit 15, No function/Reverse
Bit 15 = “0” causes no reversing.
Bit 15 = “1” causes reversing.
Note: In the factory setting reversing is set to digital in par. O-54 Reversing Select.

NB!
Bit 15 causes reversing only when Ser. communication, Logic or or Logic and is selected.