4 object and data types supported, 3 size attribute – GE Industrial Solutions AF-600 FP Profibus DP User Manual

Page 65

Advertising
background image

6.4 Object and Data Types Supported

6.4.1 Parameter and Data Type Structure Description

6.4.2 Parameter Description

PROFIBUS DP has a number of describing attributes. Read/write on parameter description is performed in the PCV part using the RC commands 4/5 and the sub-
index of the desired description element.

6.4.3 Size Attribute

The size index and the conversion index for each parameter can be taken from the parameter list in the respective Operating Instructions.

Physical unit

Size index

Measuring unit

Designation

Conversion index

Conversion factor

0

No dimension

Time

4

second

s

0

1

-1

0.1

-2

0.01

millisecond

ms

-3

0.001

minute

min

70

60

hour

h

74

3600

day

d

77

86400

Energy

8

watthour

Wh

0

1

kilowatthour

kWh

3

1000

megawatthour

MWh

6

10

6

Power

9

milliwatt

mW

-3

0.001

watt

W

0

1

kilowatt

kW

3

1000

megawatt

MW

6

10

6

Rotation

11

rotation per minute

RPM

67

1

Torque

16

newtonmeter

Nm

0

1

kilonewtonmeter

kNm

3

1000

Temperature

17

degree Celsius

ºC

0

1

Voltage

21

millivolt

mV

-3

0.001

volt

V

0

1

kilovolt

kV

3

1000

Current

22

milliampere

mA

-3

0.001

ampere

A

0

1

kiloampere

kA

3

1000

Resistance

23

milliohm

mOhm

-3

0.001

ohm

Ohm

0

1

kiloohm

kOhm

3

1000

Ratio

24

per cent

%

0

1

Relative change

27

per cent

%

0

1

Frequency

28

hertz

Hz

0

1

kilohertz

kHz

3

1000

megahertz

MHz

6

10

6

gigahertz

GHz

9

10

9

AF-650 GP/AF-600 FP Profibus DP Operating Instructions

64

6

Advertising