5.3.3 Request / Response Handling

The RC portion of the PCA word defines the requests that may be issued from the master to the slave as well as what other portions of the PCV (IND and PVA) are
involved. The PVA portion will transmit word-size parameter values in bytes 7 and 8, while long word size values require bytes 5 to 8 (32 bits). If the Response /
Request contains array elements, the IND will carry the Array Sub-index. If parameter descriptions are involved, the IND will hold the Record Sub-index of the
parameter description.

5.3.4 RC Content

Request

Function

0

No request

1

Request parameter value

2

Change parameter value (word)

3

Change parameter value (long word)

4

Request description element

5

Change description element

6

Request parameter value (array)

7

Change parameter value (array word)

8

Change parameter value (array long word)

9

Request number of array elements

10-15

Not used

If the slave rejects a request from the master, the RC word in the PPO-read
will indicate this by assuming the value 7. The fault number will be carried by
bytes 7 and 8 in the PVA element.

Response

Function

0

No response

1

Transfer parameter value (word)

2

Transfer parameter value (long word)

3

Transfer description element

4

Transfer parameter value (array word)

5

Transfer parameter value (array long word)

6

Transfer number of array elements

7

Request rejected (incl. fault #, see below)

8

Not serviceable by PCV interface

9

Not used

10

Not used

11

Not used

12

Not used

13-15

Not used

Fault
no.

Interpretation

0

Illegal PNU

1

Parameter value cannot be changed

2

Upper or lower limit exceeded

3

Subindex corrupted

4

No array

5

Data type false

6

Cannot be set by user (reset only)

7

Description element cannot be changed

8

IR required PPO-write not available

9

Description data not available

10

Access group

11

No parameter write access

12

Key word missing

13

Text in cyclical transmission not readable

14

Name in cyclical transmission not readable

15

Text array not available

16

PPO-write missing

17

Request temporarily rejected

18

Other fault

19

Data in cyclical transmission not readable

130

There is no network access to the parameter called

131

Data change is not possible because factory setup has been
selected

AF-650 GP/AF-600 FP Profibus DP Operating Instructions

51

5