GE Industrial Solutions AF-600 FP Profibus DP User Manual
Page 75
Phases
Bi-colour LED
Status
Power On
Red
The PROFIBUS card is defect.
Contact GE or your local distributor
Green
The PROFIBUS card is OK.
Search baud rate
Green
Searching for the baud rate. Check the connection to the master if it
stays in this state.
Wait Parameterizing
Green
Baud rate found - waiting for parameters from the master.
Red
Wrong parameters from the master.
Wait Configuration
Green
Parameters from master OK - waiting for configuration data.
Red
Wrong Configuration data from the master.
Data Exchange
Green
Data Exchange between the master and the frequency converter is
active.
Red
Clear State. Warning 34 is active and a network reaction in par.
O-04 Control Word Timeout Function is executed.
Table 8.1: LED 1: Net Status
Bi-colour LED
Status
No light
No PROFIBUS DPV1 communication is active.
Green
DP V1 communication from a Master Class 1 (PLC) is active.
Green
DP V1 communication from a Master Class 2 (DCT-10) is active.
Green
DP V1 communication from a Master Class 1 and 2 is active.
Red
Internal error.
Table 8.2: LED 2: Module Status
AF-650 GP/AF-600 FP Profibus DP Operating Instructions
74