Phases

Bi-colour LED

Status

Power On

Red

The PROFIBUS card is defect.
Contact GE or your local distributor

Green

The PROFIBUS card is OK.

Search baud rate

Green

Searching for the baud rate. Check the connection to the master if it
stays in this state.

Wait Parameterizing

Green

Baud rate found - waiting for parameters from the master.

Red

Wrong parameters from the master.

Wait Configuration

Green

Parameters from master OK - waiting for configuration data.

Red

Wrong Configuration data from the master.

Data Exchange

Green

Data Exchange between the master and the frequency converter is
active.

Red

Clear State. Warning 34 is active and a network reaction in par.
O-04 Control Word Timeout Function
is executed.

Table 8.1: LED 1: Net Status

Bi-colour LED

Status

No light

No PROFIBUS DPV1 communication is active.

Green

DP V1 communication from a Master Class 1 (PLC) is active.

Green

DP V1 communication from a Master Class 2 (DCT-10) is active.

Green

DP V1 communication from a Master Class 1 and 2 is active.

Red

Internal error.

Table 8.2: LED 2: Module Status

AF-650 GP/AF-600 FP Profibus DP Operating Instructions