2.1.6 Connecting the Network

Proper termination of the network is essential. A mismatch of impedance may
result in reflections on the line that will corrupt data transmission.

-

The Profibus DP Communications Module has a suitable termina-
tion, activated by switch 1 located on the Profibus option. The
switches must be on to terminate the network. The factory setting
is off.

-

Nodes at the physical ends of each segment must be terminated.

-

When power to the Profibus DP Communications Module is down,
please note that the termination is still active, although not func-
tional.

-

Most masters and repeaters are equipped with their own termina-
tion.

-

If an external termination circuit consisting of three resistors is con-
nected to the network, a 5V DC power supply must be used. Terminal
66 and 67 can be used for this.

-

The CS-pin on the Profibus connector is Control Select. When option
goes into active state and sends a message, the CS pin goes high
(+5 Volts). This can be used to control optical transmitters etc. or for
triggering measurement equipment like an oscilloscope.

-

D-sub 9 connector.
If desired, a D-sub 9 adaptor can be added as an option.
N.B.: If the D-sub 9 adaptor is used, please be aware that the ter-
mination switch on the Profibus option is set to OFF, to avoid double
termination. as the Profibus D-sub 9 connector also features a ter-
mination switch.

Illustration 2.1: 62 = RxD/TxD-P red cable (Siemens B)
63 = RxD/TxD-N green cable (Siemens A)
66 and 67 are for use with external terminator resistor only