IMPORTANT: EV Charging Station is rated for 208-240V power only. The EVSE must be connected to a
grounded, metal, permanent wiring system, or an equipment grounding conductor. This should be run
with circuit conductors and connected to the equipment grounding bar or lead on the EVSE.
Connections to the EVSE shall comply with all applicable electrical codes and ordinances.

Connect L1, L2 to the fuse block and ground wire to the ground bar shown in Figure 23.

In case of RFID sensor, the communication cable is connected to the Ethernet connector on the
controller, just like the pedestal as shown in Figure 9.

Field wiring entry from bottom:
If this option is preferred, remove the two knockouts at the bottom of the enclosure and fill in the
unused cable holes on the back of the enclosure using the spare NEMA 3R knockout plugs provided.
See Figure 30. Assemble the supplied conduit hub in the bottom and make the conduit arrangement.

Figure 28: Pole-Mount Installation, Exploded View