EV Charging Station

User Manual & Installation Instructions

GE EV Charging Station User Manual

83 of 86

4.6 Reset Controller to Factory Default

Should you have inadvertently changed to a non-default IP setting and cannot remember the IP
settings, or simply reverse to default configuration for other reasons, you can reset the controller to
the factory default values by following these steps.


Follow the instructions below to reset the controller settings:
1. Switch off EVSE main breaker to remove power to the controller.

2. Short connector J21 pins 1, 2 and 3 with a conductive connector.




3. Switch on EVSE main breaker to supply power to the controller.

4. After a few seconds switch off EVSE main breaker to remove power to the controller.

5. Remove short from connector J21.

6. Switch on EVSE main breaker to supply power to the controller.,

7. Reconfigure as desired via EVSE controller configuration server interface. See description in an
earlier chapter.

Note: It is recommended to keep track of the different IP settings for each EVSE by
recording them on the form found on the final page of this document.

Figure 77