Connecting Accessory Devices

Revision D

Smart DC Controller

4-11

User Relays - Programming Procedure

The Smart DC Controller is able to interface with many types of external devices through the use of two user-
programmable output relays. All of the user relay functions identified and described in Table 4-3 are accessible
in the Installer Menu.

NOTE

The User Relays will operate normally to less than 18VDC. The USER 2 RELAY is rated for
DC only up to 48V and does not have a N.C. (normally closed) connection.

Use the Smart DC Controller buttons to program the user relays according to the following steps:

1. Select and connect to the relay you wish to use on the Smart DC Controller board.
2. Access the Installer Menu and RL 1 or RL 2 display (depending on the relay you have connected).
3. Enter the appropriate function using the associated number (1 through 24) listed in the table.

Table 4-3. User-Programmable User Relays - Function Options

No.

Name

Description

1

Close limit output

Creates an interlock signal to another operator’s interlock input, or simply to indicate that the
gate is secure. The relay is released when the fully-closed limit switch is tripped. The relay is
energized when the fully-closed limit is released. (Any open command energizes the relay.)

2

Close limit pulse output

Used in a sequenced system to command a second machine to close. Generates a brief pulsed
output that occurs when the close limit is triggered.

3

Open limit output

Indicates a full-open position. This output becomes active when an open-limit is triggered
and releases when the open-limit is released.

4

Open limit pulse output

Trips a sequenced barrier arm gate operator to open. Generates a brief pulsed-output when
the open-limit is triggered. An additional pulse is also generated with any new open command
even when the gate is already fully-opened.

5

Warn before/during operate
output

Controls an external warning device. This output operates at the same time as the internal
warn before operate buzzer.

6

Gate Lock output

Controls external solenoid locks or magnetic locks. In both directions of travel, this output is

activated about 7/10

ths

of a second before the operator starts moving the gate and remains

active while moving as well as for a few seconds after stopping.

7

Gate forced open output

Activated if the gate is forced off the closed limit switch and operator is not able to restore the
gate to full closed within four seconds. This alarm resets itself in 30 seconds.

8

Gate open too long output

Activates when the gate is open longer than a user-selected period of time. Adjustable from 0
delay to 135 seconds delay in 30-second time increments.
Note: TL - OPEN TIME ALERT adjustments can be made in the Installer Menu.

9

Safety Mode Alert output

Activated when system is in Safe Mode or entrapment mode.

10

Entrapment Mode Alert output

Activated only when system is in the Entrapment Mode.

11

Unauthorized Vehicle Entry
output

Activated when a second vehicle enters from the outside without a valid input from an access
control device. This output releases when an access control input signals open or the gate
reaches the close limit position.

12

Outside Obstruction Vehicle
Detector output

Interlocks an entry device to prevent pedestrian use. This output is active whenever the
Outside Obstruction Loop Detector is tripped.