Power cords – Brocade DCX 8510-8 Backbone Hardware Reference Manual User Manual

Page 133

Advertising
background image

Power supply requirements

TABLE 24

Demand

Power supplies @ 110 VAC (nominal)

Power supplies @ 220 VAC (nominal)

Up to 1000W

2

2

1000W-2000W

4

2

Greater than 2000W

NA - cannot achieve redundancy

4

In addition to these tables, you can consult the power tables in the latest update of the Fabric OS
Release Notes.

Power cords

The types of power cords provided with the Brocade DCX 8510-8 are specific to the country where it is
installed. For each of the types of power cords in the following table, the end that connects to the
Brocade DCX 8510-8 has an IEC 60320/C19 cable connector. The AC power receptacles on each
power supply are equipped with IEC 60320/C20 power connectors.

In order to connect to a power strip already installed in a cabinet, the C20, 20A-250V, 12 AWG power
cord is required.

To order a power cord, contact your Brocade DCX 8510-8 supplier.

Power cord types (international)

TABLE 25

Plug style

NEMA
5-20P125V
onlyUSA,
Canada,
Mexico,
other
locations

NEMA
L6-20USA,
Canada,
Mexico,
other
locations

CEE-7/7
"Schuko"
Continental
Europe

BS-1363A AS 3112

Australia /
New
Zealand

IEC-6030932A-6h,
230V~

C20
20A-250V12
AWG
connect to
in-cabinet
power strip
only All
locations

Country

Argentina

X

X

Australia

X

X

Austria

X

X

Bahrain

X

X

Belgium

X

X

Power cords

Brocade DCX 8510-8 Backbone Hardware Reference Manual

133

53-1002180-07

Advertising