Completing the replacement, Proceed to – Brocade DCX 8510-8 Backbone Hardware Reference Manual User Manual

Page 89

Advertising
background image

The system is coming up, please wait...

.

.

.

Fri Jun 18 14:53:13 2010: Doing firmwarecommit now.

Please wait ...

Fri Jun 18 14:55:27 2010: Firmware commit completes successfully.

Validating the filesystem ...

Fri Jun 18 22:36:05 2010: Doing firmwarecommit now.

Please wait ...

Fri Jun 18 22:36:48 2010: Firmware commit completes successfully.

2010/06/18-14:56:50, [SULB-1004], 908, SLOT 7 | CHASSIS, INFO, Brocade_DCX,

Firmwarecommit has completed.

2010/06/18-14:56:50, [SULB-1036], 909, SLOT 7 | CHASSIS, INFO, Brocade_DCX, The

new Version: Fabric OS v6.3.0c

2010/06/18-14:56:50, [SULB-1002], 910, SLOT 7 | CHASSIS, INFO, Brocade_DCX,

Firmwaredownload command has completed successfully.

NOTE
The time stamp on the co-CPU may not be in sync with the main CPU on the blade. This is not a
cause for concern.

8. Log back in to the standby CP blade and enter firmwareDownloadStatus on the standby CP blade

to validate a successful commit. This may take 10 minutes.

9. If you are upgrading through several levels of the Fabric OS, repeat step 5 through step 8 as often as

necessary based on the path outlined in the preceding table. Otherwise, proceed to step 10.

10.Log out of the standby CP blade and log in to the active CP blade.
11.Proceed to

Completing the replacement

on page 89

Completing the replacement

Complete the following steps to complete the CP8 control blade replacement procedure.

1. Enter haEnable to re-enable HA on the active CP blade.

NOTE
For Fabric OS 7.0.0 and later, haEnable will cause the standby CP blade to reboot. Wait until POST
completes before moving to the next step. POST is complete when the Status LED on the CP blade
returns to a steady green state.

2. Enter haShow and verify that the command output includes "HA Enabled, Heartbeat Up". If it is not

yet enabled, re-enter the command until you have verified that redundancy is achieved.

DCX_124:admin> hashow

Local CP (Slot 7, CP1) : Active

Remote CP (Slot 6, CP0) : Standby, Healthy

HA Enabled, Heartbeat Up, HA State Synchronized

3. Enter firmwareShow to verify that the firmware version has been updated and that the versions are

the same on the two CP blades. The slot numbers will be different for the DCX 8510-4 or DCX-4S.
(not all slot numbers are shown).

DCX_8510:admin> firmwareshow

Slot Name Appl Primary/Secondary Versions Status

-----------------------------------------------------------

4 FX8-24 FOS v7.0.0

v7.0.0

6 CP0 FOS v7.0.0 STANDBY

v7.0.0

7 CP1 FOS v7.0.0 ACTIVE *

v7.0.0

10 FX8-24 FOS v7.0.0

v7.0.0

Completing the replacement

Brocade DCX 8510-8 Backbone Hardware Reference Manual

89