Downloading firmware from an ftp server, Table 11, Downloading firmware from an – Brocade DCX 8510-8 Backbone Hardware Reference Manual User Manual

Page 87: Ftp server

Advertising
background image

If you are using a USB device to download the firmware, skip to

Downloading firmware from a USB

device

on page 88. If the firmware on the standby CP blade is more than one level down from the

level on the active CP blade, you must have formatted USB devices for each of the versions you will
need to upgrade.

Steps for upgrading through multiple versions of Fabric OS

TABLE 11

Current Fabric OS version Target Fabric OS version Upgrade steps

7.0.0

7.0.0x

Use firmwaredownload -s to upgrade directly to
7.0.0x

Downloading firmware from an FTP server

For this task, refer to

Verifying operation of the new CP blade

on page 86 for the correct sequence of

upgrading firmware versions to reach your target version.

Complete the following steps to download the firmware from an FTP server.

1. Log in to the standby CP blade as admin. If you need to know the IP address of the standby blade,

run ipaddrshow .

You should remain logged in to the active CP blade in order to monitor it.

2. Run firmwareDownload -s to download the firmware to the standby CP blade. The -s option also

disables the autoreboot, so you will have to manually issue a reboot after the download finishes to
initiate firmwarecommit. Enter all requested information (use default values).

3. When the download process finishes, run firmwareDownloadStatus to verify that the firmware has

been updated.The command displays a running account of the progress of the firmwareDownload
command (if it is still running) until the command has completed. The final message is similar to the
following and will appear with a date and time stamp:

Slot 6 (CP0, active): Firmwaredownload command has completed successfully. Use

firmwareshow to verify the firmware versions.

4. On the standby CP blade (the blade for which you just changed the firmware level), run reboot. The

reboot of the standby CP will initiate a firmwarecommit to the secondary partition and log you out.

DCX_124:admin> reboot

Broadcast message from root (ttyS0) Fri Jun 18 14:49:45 2010...

The system is going down for reboot NOW !!

INIT: Switching to runlevel: 6

INIT: Sending processes the TERM signal DCX_124:admin> HAMu Heartbeat down, stop

FSS

Unmounting all f##exiting due to signal: 9, pending signals: 0x20000, 0x0

ilesystems.

Please stand by while rebooting the system...

Restarting system.

The system is coming up, please wait...

.

.

.

Fri Jun 18 14:53:13 2010: Doing firmwarecommit now.

Please wait ...

Fri Jun 18 14:55:27 2010: Firmware commit completes successfully.

Validating the filesystem ...

Fri Jun 18 22:36:05 2010: Doing firmwarecommit now.

Please wait ...

Fri Jun 18 22:36:48 2010: Firmware commit completes successfully.

2010/06/18-14:56:50, [SULB-1004], 908, SLOT 7 | CHASSIS, INFO, Brocade_DCX,

Firmwarecommit has completed.

2010/06/18-14:56:50, [SULB-1036], 909, SLOT 7 | CHASSIS, INFO, Brocade_DCX, The

new Version: Fabric OS v6.3.0c

2010/06/18-14:56:50, [SULB-1002], 910, SLOT 7 | CHASSIS, INFO, Brocade_DCX,

Firmwaredownload command has completed successfully.

Downloading firmware from an FTP server

Brocade DCX 8510-8 Backbone Hardware Reference Manual

87