Power demands per component

TABLE 22

Blade or fan
units

Maximum Power
Draw (Watts)

Type of Blade Ports per blade

Number of
blades
permitted in
chassis

Total ports per
chassis

CP8

40

Control blade

NA

2

NA

CR16-4

135

Core blade

8 64-Gbps QSFP
ports

2

16 quad ports
(64 ports)

FC8-32E

140

Port blade

32 8-Gbps SFP+

up to 4

128

FC8-48E

160.4

Port blade

48 8-Gbps SFP+

up to 4

192

FC8-64

126.4

Port blade

64 8-Gbps SFP+

up to 4

256

FC16-32

140

Port blade

32 16-Gbps SFP+-
can use 8 Gbps SFP
+

up to 4

128

FC16-48

160.4

Port blade

48 16-Gbps SFP+-
can use 8 Gbps SFP
+

up to 4

192

FC16-64

134

Port blade

16 QSFPs (4 16-
Gbps ports per
QSFP)

up to 4

256

FS8-18

235

Encryption
blade

16 8-Gbps SFP+

up to 4

64

FX8-24

250

Extension
blade

12 8-Gbps SFP+

10 1-Gbps Ethernet

2 10-Gbps Ethernet

up to 4

48 8-Gbps

40 1-Gbps
Ethernet

8 10-Gbps
Ethernet

Fan unit

90

NA

NA

2 fans per
chassis

NA

Power supply redundancy is key to your installation, so any demand must be met with twice the
capacity. Refer to the following table for power supply requirements for specific demand ranges.

Power supply requirements

TABLE 23

Demand

Power supplies @ 110 VAC (nominal)

Power supplies @ 220 VAC (nominal)

Up to 1000W

2

2

1000W-2000W

NA - cannot achieve redundancy

2

Specifications