Downloading firmware from a USB device

For this task, determine the correct sequence of upgrading firmware versions to reach your target
version.

Complete the following steps to download the firmware from a USB device.

This section assumes that the new firmware has already been copied onto the USB device. The folder
structure on the USB device must be as follows in order to allow the device to be enabled:

• brocade>

config

firmware

firmwareKey

support

The firmware folder contains the folder for the specific release you are installing.

1. Insert the USB device into the active CP blade.
2. Attach a serial cable from the PC to the active CP blade.
3. Log in to the active CP blade as admin if you are not still logged in and enter usbStorage -e to

enable the USB device.

4. Remove the serial cable from the active CP blade and attach it to the standby CP blade and log in

as admin.

5. Run firmwareDownload -s to download the firmware to the standby CP blade. The -s option also

disables the autoreboot, so you will have to manually issue a reboot after the download finishes to
initiate firmwarecommit. Enter all requested information (use default values).

6. When the download process finishes, run firmwareDownloadStatus to verify that the firmware has

been updated. The command displays a running account of the progress of the firmwareDownload
command until the command has completed. The final message is similar to the following and will
appear with a date and time stamp:

Slot 4 (CP0, active): Firmwaredownload command has completed successfully. Use

firmwareshow to verify the firmware versions.

7. Ensure that you are still logged in to the standby CP blade (the blade for which you just changed

the firmware level) and type reboot. The reboot of the standby CP will initiate a firmwarecommit to
the secondary partition and log you out.

DCX_124:admin> reboot

Broadcast message from root (ttyS0) Fri Jun 18 14:49:45 2010...

The system is going down for reboot NOW !!

INIT: Switching to runlevel: 6

INIT: Sending processes the TERM signal DCX_124:admin> HAMu Heartbeat down, stop

FSS

Unmounting all f##exiting due to signal: 9, pending signals: 0x20000, 0x0

ilesystems.

Please stand by while rebooting the system...

Restarting system.

The system is coming up, please wait...

.

.

.

Fri Jun 18 14:53:13 2010: Doing firmwarecommit now.

Please wait ...

Fri Jun 18 14:55:27 2010: Firmware commit completes successfully.

Validating the filesystem ...

Fri Jun 18 22:36:05 2010: Doing firmwarecommit now.

Please wait ...

Fri Jun 18 22:36:48 2010: Firmware commit completes successfully.

2010/06/18-14:56:50, [SULB-1004], 908, SLOT 7 | CHASSIS, INFO, Brocade_DCX,

Firmwarecommit has completed.

2010/06/18-14:56:50, [SULB-1036], 909, SLOT 7 | CHASSIS, INFO, Brocade_DCX, The

new Version: Fabric OS v6.3.0c

2010/06/18-14:56:50, [SULB-1002], 910, SLOT 7 | CHASSIS, INFO, Brocade_DCX,

Firmwaredownload command has completed successfully.

Downloading firmware from a USB device

76