B.2 template 2: single zone system with horn, B.2: template 2: single zone system with horn – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 122

Advertising
background image

122

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

FACP Configuration Templates

Template 2: Single Zone System With Horn

B.2 Template 2: Single Zone System With Horn

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).

Input Zone Types:

Zone 1 = circuit with type code of 2-wire smoke

Zone 2 = circuit with type code of 2-wire smoke

Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release

Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)

Zone 5 = circuit with type code of Pull Station

Zone 6 = circuit with type code of Supervisory

Output Circuit Types:

Output 1 = Release Circuit 1 - Unsupervised for shorts

Output 2 = Release Stage NAC - silenceable, programmed Release Stage operation (refer to

“Release Stage/NAC Operation” on page 98)

Output 3 = Alarm NAC - silenceable, coded for steady on

Output 4 = Alarm NAC - silenceable, coded for steady on

Timers

Pre-Discharge Delay - set for 30 seconds

Discharge - set for 1 minute

Waterflow Delay Timer - set for 90 seconds

AC Loss Delay Timer - set for 2 hours

Template 2: Single Zone System with Horn

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE

ABORT

PULL

STATION

SUPERVISORY

#1 RELEASE CIRCUIT 1

X

X

X

X

#2 RELEASE STAGE NAC

Xr

Xr

Xr

#3 ALARM NAC

X

#4 ALARM NAC

X

X

X

Advertising