5 on-board relays, On-board relays – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 69

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

69

Master Programming Level

Programming

3.5.5 On-Board Relays

Pressing 2 while viewing Programming Screen #2 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:

To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screen will be displayed:

Pressing 1 for Type will display the following screens:

While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.

Pressing 2 for Latching will toggle the display between Latching Yes and No.

If Latching Yes is selected, when the Relay is activated, the condition causing the activation must be
cleared and the FACP must be reset to clear the Relay.

If Latching No is selected, when the Relay is activated, the Relay will reset as soon as the condition
causing the activation is cleared. The FACP does not need to be reset.

ON-BOARD RELAYS

1=RELAY 1

2=RELAY 2

3=RELAY 3

Relays Selection Screen

RELAY #

1=TYPE ALARM

2=LATCHING NO

Relay Programming Screen

RELAY TYPE

1=ALARM

2=TROUBLE

3=SUPERVISORY

Relay Screen #1

RELAY TYPE

1=PRE-DISCHARGE

2=DISCHARGE

3=AC LOSS

Relay Screen #2

Advertising
This manual is related to the following products: