MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

13

Section 1: Product Description

The MRP-2002 is a six zone FACP for single and dual hazard agent releasing applications. The
FACP provides reliable fire detection, signaling and protection for commercial, industrial and insti-
tutional buildings requiring agent-based releasing. The FACP is compatible with System Sensor’s
i

3

detectors which are conventional smoke detectors that can transmit a maintenance trouble signal

to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient
temperature falls below the detector rating of approximately 45

o

F (refer to System Sensor for i

3

Installation and Maintenance Instructions). In addition, the control panel is compatible with con-
ventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations,
waterflow devices, tamper switches and other normally-open contact devices. Refer to Device
Compatibility Document for a complete listing of compatible devices.

Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids.
Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory)
and 24 VDC special application resettable and nonresettable power outputs are also included on the
main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.

Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicator, display alarm information on
the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate
an optional module used to notify a remote station or initiate an auxiliary control function.

The MRP-2002C is a ULC approved Canadian version of the FACP which offers the same features
as the MRP-2002 but is supplied standard with a dress panel and one built-in ANN-LED annuncia-
tor.

The MRP-2002E offers the same features as the MRP-2002 but allows connection to 220/240 VAC.

Unless otherwise specified, the information in this manual applies to all versions of the panel.

1.1 Product Features

Six programmable Style B (Class B) IDCs (Initiating Device Circuit)

Four programmable Style Y (Class B) output circuits - (special application power)

Three programmable Form-C relays

7.0 amps total 24 VDC output circuit current

Resettable and non-resettable output power

Built-in Programmer

ANN-BUS for connection to optional:

ANN-80 Remote LCD Annunciator

ANN-I/O LED Driver

ANN-S/PG Printer Module

ANN-RLY Relay Module

ANN-LED Annunciator Module

80-character LCD display (backlit)

Real-time clock/calendar with daylight savings time control

History log with 256 event storage

Control Buttons

ACK (Acknowledge)

Alarm Silence

System Reset/Lamp Test

Drill

Advertising