6 installation of optional modules, 1 cac-5x class a converter module, Installation – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 31: Installation of optional modules, Cac-5x class a converter module

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

31

Installation of Optional Modules

Installation

2.6 Installation of Optional Modules

2.6.1 CAC-5X Class A Converter Module

Installation

The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class
A). Two CAC-5X Modules are required to convert all Output Circuits and/or Initiating Device Cir-
cuits to Class A. The modules plug into connector J2 which is located at the top left of the main
circuit board and J7 which is located at the top center of the main circuit board.

To install the CAC-5X, remove the two main circuit board mounting screws referenced in the fol-
lowing illustration and replace with the two supplied male/female standoffs in the locations indi-
cated in the following figure. Carefully align the connector on the CAC-5X with J2 on the FACP
main circuit board and press the module securely into place. Make certain the pins are properly
aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to the standoffs
with the screws that were just removed.

To install the second CAC-5X on J7, remove the main circuit board mounting screw referenced in
the following illustration and replace with the supplied male/female standoff. Insert the supplied
plastic standoff in the location indicated in the following illustration. Carefully align the connector
on the CAC-5X with J7 and press the module securely into place. Make certain the pins are prop-
erly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to the metal
standoff with the screw that was just removed.

!

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.

Figure 2.13 CAC-5X Module Installation

Main Circuit Board

Metal
Standoff

Plastic
Standoff

CAC-5X Module

rp

200

1ca

c5m

nt

.cdr

CAC-5X Module

Metal
Standoff

Metal
Standoff

Installation on J2 Connector

Installation on J7 Connector