MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

NFPA Standard-Specific Requirements

Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts

C.2 Central Station/Remote Station Transmitter: Connection

to FACP Dry Contacts

The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer’s manual for details.

Figure C.5 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter

Typical Central Station/Remote Station Transmitter Module

Typical Input Zone Triggers

Fire Alarm Control Panel

Alarm

Superv

.

T

ro

ubl

e*

*Note: The Trouble Relay is a
fail-safe relay. With power
applied to the FACP and no
troubles in the panel, the wiring
should be contacted to the NO
and C contacts as indicated in the
illustration.