3 ann-sec option card, Ann-sec option card – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 34

Advertising
background image

34

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Installation

Installation of Optional Modules

Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building

Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended

for connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:

Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building

Before installing the module, place the disconnect switch to the down (disconnect) position to pre-
vent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after
the module is installed in the FACP. In addition, the System Trouble indicator will turn on to indi-
cate the Disconnect condition.

2.6.3 ANN-SEC Option Card

The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.

1. Remove the chassis mounting screw to the right of TB3 and replace it with the supplied

0.5” x 4-40 male-female standoff.

2. Install header J1 on the ANN-SEC into J13 on the main circuit board.

Figure 2.16 4XTMF Transmitter Module

Connect to FACP Connectors J4 & J5

Disconnect
Switch
shown in
disconnect
position

TBL Jumper

Remote Alarm (power-limited)*

Remote Trouble (power-limited)*

No connection

Municipal Box (nonpower-limited)*

1+
2-
3+
4-
5
6+
7-

Polarities are shown for module activation

Note: 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal. For an
application using reverse polarity of a supervisory signal, refer to the Appendix titled “FACP with
Keltron” on page 165.

* Wiring from these terminals
can exit the protected premises.
Dummy load terminals 6 and 7
(4.7k

, ¼ watt resistor) if

Municipal Box is not connected.

Disconnect LED

4

xtm

f.w

m

f

Advertising
This manual is related to the following products: