2.7.5 ANN-I/O LED Driver Module

The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The following sections describe hardware installation. Refer to the section
titledSection 3.5.7, “ANN-BUS”, on page 78 for programming information.

ANN-I/O Board Layout

Figure 2.22 illustrates the ANN-I/O board showing locations of screw terminals for connection to
the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID
number.

Specifications

Max. ANN-BUS Voltage: 28 VDC

Max. Current:

Alarm: 200 mA

Standby: 35 mA

Each LED: 10 mA

Operating Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

For indoor use in a dry location only

Figure 2.22 ANN-I/O Board Layout

ANN-BUS (ID#)
Address DIP
switch

ANN-BUS Connector

Terminals not used (future)