MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Installation

Power-limited Wiring Requirements

2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter
and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is illus-
trated below.

Figure 2.12 Typical UL Power-limited Wiring Requirements

Power-limited Circuits

(Class 2)

Power-limited

Circuits

(Class 2)

Nonpower-
limited
Circuit

AC Power

120 VAC

Hot (L1)

Ground

Neutral (L2)

CAC-5X

rp

20

01

cu

lwire

.wmf

4XTMF

CAC-5X

ground

stud

Power-limited Circuits (Class 2)

Nonpower-
limited
Circuit

Power-limited
Circuit
(Class 2)

Nonpower-limited Circuits*

*Note: In certain applications, an NAC (power-limited circuit) could be adjacent to a

releasing circuit (nonpower-limited without supervision kit REL-4.7K)

Agent Releasing FACP