FACP Configuration Templates

Template 12: Agent/Waterflow - Single Detector

B.12 Template 12: Agent/Waterflow - Single Detector

Table Legend:

* = shows relationship only, will not activate a release circuit

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).

Input Zone Types:

Zone 1 = circuit with type code of 2-wire smoke

Zone 2 = circuit with type code of 2-wire smoke

Zone 3 = circuit with type code Manual Release/Abort Switch Combo - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 71)

Zone 4 = circuit with type code of Discharge Pressure Switch

Zone 5 = circuit with type code of Waterflow

Zone 6 = circuit with type code of Supervisory

Output Circuit Types:

Output 1 = Release Circuit 1 - Supervised for shorts

Output 2 = Release Circuit 2 - Supervised for shorts

Output 3 = Alarm NAC - silenceable, steady on

Output 4 = Release Stage Coded - nonsilenceable, programmed Release Stage Coded operation
for Release Circuit 1 (refer to“Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 66
)

ANN-BUS

Enabled = Yes

Address 1: ANN-RLY

Timers

Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 0 seconds

Discharge: Release 1 - set for Always On; Release 2 - set for Always On

Waterflow Delay Timer - set for 90 seconds

AC Loss Delay Timer - set for 2 hours

Template 12: Agent/Waterflow - Single Detector

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE/AB

ORT SW.

COMBO

DISCHARGE

PRESSURE

WATERFLOW

SUPERVISORY

#1 RELEASE CIRCUIT 1

X

X

X

X*

#2 RELEASE CIRCUIT 2

X

X

X

X*

#3 ALARM NAC

X

X

X

X

X

#4 RELEASE STAGE
CODED

Xr

Xr

Xr

Xr