52

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Programming

Master Programming Level

If the Maintenance level password (default 11111) is entered, the following screen will appear:

Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.

3.5 Master Programming Level

When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble indicator flashes until Programming mode is exited. The following display will
appear:

The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as
illustrated below while pressing the ‘up’ arrow key will display the previous screen.

PROGRAMMING

1=INPUT ZONES

2=HISTORY

3=WALKTEST

PROGRAMMING

1=FACP CONFIG T1

2=INPUT ZONES

3=OUTPUT CIRCUITS

Programming Screen #1