B.9 template 9: dual hazard - cross-zone, B.9: template 9: dual hazard - cross-zone – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 143

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

143

Template 9: Dual Hazard - Cross-Zone

FACP Configuration Templates

B.9 Template 9: Dual Hazard - Cross-Zone

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).

Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.

Input Zone Types:

Zone 1 = circuit with type code of 2-wire smoke

Zone 2 = circuit with type code of 2-wire smoke

Zone 3 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 71)

Zone 4 = circuit with type code of 2-wire smoke

Zone 5 = circuit with type code of 2-wire smoke

Zone 6 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 71)

Output Circuit Types:

Output 1 = Release Circuit 1 - Supervised for shorts

Output 2 = Release Circuit 2 - Supervised for shorts

Output 3 = Horn NAC - silenceable, programmed Cross-Zone coding operation for Release
Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66)

Output 4 = Horn NAC - silenceable, programmed Cross-Zone coding operation for Release
Circuit 2 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66)

Timers

Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 30 seconds

Discharge: Release 1 - set for Always On; Release 2 - set for Always On

Waterflow Delay Timer - set for 90 seconds

AC Loss Delay Timer - set for 2 hours

Template 9: Dual Hazard - Cross-Zone

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE/ABORT

SW. COMBO

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE/ABORT

SW. COMBO

#1 RELEASE CIRCUIT 1

C1

C1

X

#2 RELEASE CIRCUIT 2

C2

C2

X

#3 HORN NAC

Xc

Xc

X

#4 HORN NAC

Xc

Xc

X

Advertising