C.1 nfpa 72 auxiliary fire alarm system, C.1: nfpa 72 auxiliary fire alarm system, Fire – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 161

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

161

NFPA 72 Auxiliary Fire Alarm System

NFPA Standard-Specific Requirements

C.1 NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.

Notes:

1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the MRP-2002 main circuit board to supervise placement of 4XTMF module and

circuit.

3. Cut JP24 on the MRP-2002 main circuit board to enable FACP Supervisory relay.
4. Refer to “4XTMF Municipal Box Transmitter Option Module” on page 33 for detailed

information.

FIRE

Gamewell Model M34-56 Local

Energy Municipal Box

Polarities shown in alarm condition

+

Nonpower-limited

Municipal Box Circuit

+

_

-

4XTMF

Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module