Abort type, Timers, Abort type timers – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 71

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

71

Master Programming Level

Programming

Abort Type

The Abort function provides the ability to stop an agent release that was initiated by an automatic
detection device. The Abort Type provides the programmer with four abort methods:

UL (UL 864 approved) - A releasing event starts the Pre-discharge timer. If the Abort
Switch is pressed while the Delay Timer continues to count down, the timer counts down to
10 seconds and holds there. If the Abort Switch is released, the timer resumes the
countdown from 10 seconds.

IRI (UL 864 approved)- This Abort Type functions the same way as the UL type, except
that the Abort Switch will not function unless it is pressed before the cross-zoned second
input device activates

NYC - A releasing event starts the Pre-discharge timer. Pressing an Abort switch will stop
the Pre-discharge timer. Releasing the Abort switch resets the Pre-discharge timer to the
original time plus 90 seconds. The Abort switch can be operated multiple times, with each
operation resetting the Pre-discharge timer to the original time plus 90 seconds.

Local Jurisdiction - A releasing event starts the Pre-discharge timer. Pressing an Abort
switch will stop the Pre-discharge timer. Releasing the Abort switch resets the Pre-
discharge timer to the original time. The Abort switch can be operated multiple times, with
each operation resetting the Pre-discharge timer to the original time.

Timers

Timers for Pre-discharge, Discharge, Waterflow Delay and AC Loss Delay can be programmed by
pressing 2 while viewing System Setup Screen #1. The following screens will be displayed:

NOTE: The Abort functions will not operate if the Pre-discharge Delay timer is set to zero. Also,
activation of a Manual Release Switch will override Pre-discharge Delay and override an active
Abort Release Switch, resulting in an immediate agent release.

SYSTEM SETUP

1=ABORT TYPE
2=TIMERS
3=BANNER

System Setup Screen #1

TIMERS

1=PRE-DISCHARGE1 60S

2=PRE-DISCHARGE2 60S

3=DISCHARGE1 1MIN

Timer Screen #1

TIMERS

1=DISCHARGE2 1MIN

2=WATERFLW DELAY 90S

3=AC LOSS DELAY 2HR

Timer Screen #2

Advertising
This manual is related to the following products: