Appendix F: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each
circuit. Reference the chart below to specify wire requirements and limitations for each circuit.

CIRCUIT CONNECTIONS

WIRE REQUIREMENTS

Circuit Type

Circuit Function

Wire Type and Limitations

Recommended

Max. Distance

Feet (meters)

Wire Gauge

Initiating Device
Circuit
(power-limited)

Connects to
Initiating Devices

Untwisted, unshielded wire
(maximum loop resistance
not to exceed 100 ohms)

Distance limitation
set by 100 ohm
resistance limitation

12-18 AWG (3.25 - 0.75 mm

2

)

ANN-BUS (EIA-485)
power-limited

Communication for
ANN-BUS
annunciator and
relay modules

Twisted pair a maximum
loop resistance of 120 ohms

6,000 (1,800 m)

12-18 AWG (3.25 - 0.75 mm

2

)

ANN-BUS Power

Power for
ANN-BUS
annunciators

Refer to Table 2.1, “Wiring Distances,” on page 36 for information on device wiring.

24 VDC Regulated,
resettable,
nonresettable

Power for
accessories and
4-wire devices

Untwisted, unshielded wire

Distance limitation
set by 4 volt
maximum line drop

12-18 AWG (3.25 - 0.75 mm

2

)

Auxiliary Trouble
Input

Open Collector
trouble input for
CHG-75,
CHG-120F, etc.

Single conductor

Distance limitation
20 feet in same
room

18 AWG (0.75 mm

2

)

NAC/Solenoid
Outputs

Connects to NAC
devices or Release
devices

Untwisted, unshielded pair
wire

Refer to Section F.1 on page 169.

Table F.1 FACP Wire Specifications