MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

FACP Configuration Templates

Template 6: Single Hazard - Cross-Zone NAC

B.6 Template 6: Single Hazard - Cross-Zone NAC

Table Legend:

* = shows relationship only, will not activate a release circuit

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).

Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.

Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).

Input Zone Types:

Zone 1 = circuit with type code of 2-wire smoke

Zone 2 = circuit with type code of 2-wire smoke

Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release

Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)

Zone 5 = circuit with type code of Discharge Pressure Switch

Zone 6 = circuit with type code of Supervisory

Output Circuit Types:

Output 1 = Release Circuit 1 - Supervised for shorts

Output 2 = Alarm NAC - silenceable, programmed for Cross-Zone coded operation for
Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 66
)

Output 3 = Release Stage Pre-Discharge - silenceable, programmed Release Stage Pre-
Discharge operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or
Release Circuit 2:” on page 66)

Template 6: Single Hazard - Cross-Zone NAC

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE

ABORT

DISCHARGE

PRESSURE

SUPERVISORY

#1 RELEASE CIRCUIT 1

C1

C1

X

X*

X*

#2 ALARM NAC

Xc

Xc

#3 RELEASE STATE
PRE-DISCHARGE

Xr

Xr

Xr

Xr

#4 RELEASE STAGE
DISCHARGE

Xr

Xr

Xr

Xr