Master Programming Level

Programming

The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3
for Output 3 or, on the next screen, 1 for Output 4.

To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:

Enabled

Pressing 1 while viewing Output Screen #1 will cause the display to change to Enabled No. This
will prevent the selected main circuit board NAC from activating its devices. Each press of the 1
key will cause the display to toggle between Enabled Yes and Enabled No.

Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is enabled.
The exception is when a Release Circuit is disabled, a supervisory will be logged on the FACP until
the circuit is enabled.

Type

Pressing 2 while viewing Output Screen #1 will cause the following screen to be displayed:

OUTPUT #

1=ENABLED YES

2=TYPE RELEASE CIR 1

UNSUPV SHORTS

Output Screen #1

Output Screen #2

OUTPUT #

1=SILENCE N/A

2=AUTO SILENCE N/A

3=SIL INHIBIT NO

Output Screen #3

OUTPUT #

1=CODING

N/A

NAC #

1=ENABLED

2=TYPE ALARM NAC

NAC Screen #1

EDIT OUTPUT # TYPE

1=RELEASE CIRCUIT 1

2=RELEASE CIRCUIT 2

3=ALARM NAC

Edit Output # Type Screen