Template 3: Single Hazard - Cross-Zone

FACP Configuration Templates

B.3 Template 3: Single Hazard - Cross-Zone

Table Legend:

* = shows relationship only, will not activate a release circuit

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to Cross Zone in “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).

Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.

Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).

Input Zone Types:

Zone 1 = circuit with type code of 2-wire smoke

Zone 2 = circuit with type code of 2-wire smoke

Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release

Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)

Zone 5 = circuit with type code of Discharge Pressure Switch

Zone 6 = circuit with type code of Supervisory

Output Circuit Types

Output 1 = Release Circuit 1 - Supervised for shorts

Output 2 = Alarm NAC - silenceable, programmed for cross-zone coded operation for Release
Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66.)

Output 3 = Release Stage Pre-Discharge - silenceable, programmed Release State Pre-
Discharge operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or
Release Circuit 2:” on page 66.)

Output 4 = Release Stage Discharge - nonsilenceable, programmed Release Stage Discharge
operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit
2:” on page 66.)

Template 3: Single Hazard - Cross-Zone

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE

ABORT

DISCHARGE

PRESSURE

SUPERVISORY

#1 RELEASE CIRCUIT 1

C1

C1

X

X*

X*

#2 ALARM NAC

Xc

Xc

#3 RELEASE STAGE
PRE-DISCHARGE

Xr

Xr

Xr

Xr

#4 RELEASE STAGE
DISCHARGE

Xr

Xr

Xr

Xr