B.13 template 13: hp co2 single detector, B.13: template 13: hp co2 single detector – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 155

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

155

Template 13: HP CO2 Single Detector

FACP Configuration Templates

B.13 Template 13: HP CO2 Single Detector

Table Legend:

* = shows relationship only, will not activate a release circuit

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 98).

Input Zone Types:

Zone 1 = circuit with type code of 2-wire heat

Zone 2 = circuit with type code of 2-wire heat

Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release

Zone 4 = circuit with type code of Discharge Pressure Switch

Zone 5 = circuit with type code of Supervisory

Zone 6 = circuit with type code of Supervisory

Output Circuit Types:

Output 1 = Release Circuit 1 - Supervised for shorts

Output 2 = Release Circuit 2 - Supervised for shorts

Output 3 = Alarm NAC - silenceable, programmed for Cross-Zone operation for Release
Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66)

Output 4 = Release Stage Discharge - silenceable, programmed Release Stage Discharge
operation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit
2:” on page 66)

Timers

Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 30 seconds

Discharge: Release 1 - set for Always On; Release 2 - set for Always On

Waterflow Delay Timer - set for 90 seconds

AC Loss Delay Timer - set for 2 hours

Template 13: HP CO2 Single Detector

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

HEAT

2-WIRE

HEAT

MANUAL

RELEASE

DISCHARGE

PRESSURE

SUPERVISORY

SUPERVISORY

#1 RELEASE CIRCUIT 1

X

X

X

X*

#2 RELEASE CIRCUIT 2

X

X

X

X*

#3 ALARM NAC

X

X

X

X

#4 RELEASE STAGE
DISCHARGE

Xr

Xr

Xr

Xr