Output Circuits

Stat-X Aerosol Generators

Figure 2.9 shows typical wiring for Stat-X devices using the Ematch Protection Device
(P/N 3005014).

Notes:

1. Each Stat-X device requires an Ematch Protection Device to protect against high voltage

transient signals, such as lightning, that may cause the device to accidentally release.

2. Multiple Stat-X devices can be connected in series (as shown).
3. No more than ten (10) Stat-X devices can be connected on a single releasing circuit.
4. An REL-4.7K can be installed on a single Stat-X device for short circuit detection. for

multiple Stat-X devices installed in series, the REL-4.7K is installed on the last device on the
releasing circuit (as shown). An REL-4.7K is required for ULC applications.

Figure 2.9 Wiring Stat-X Devices

Releasing Circuit

+

-

Stat-X

Stat-X

Stat-X

green

yellow

black

red

Ematch Protection
Device (P/N 3005014)

REL-4.7K

st

atxmultie

o

l.wmf