MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

29

Output Circuits

Installation

2.4.2 Special Application DC Power Output Connections

Special Application Resettable and Nonresettable 24 VDC power is available on the MRP-2002
control panel.

2.4.3 Relays - Programmable

The MRP-2002 control panel provides a factory default programmed alarm relay, fail-safe trouble
relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer
to Section 3.5.5, “On-Board Relays”, on page 69). Each Form-C relay is rated for 2 amps @
30VDC (resistive) and 0.5 amps @ 30 VAC (resistive).

Note that relay connections must be power-limited.

Figure 2.10 Special Application Auxiliary Power

Special Application
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors can be
obtained from these terminals (power-limited)

Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be obtained
from these terminals (power-limited)

Jumper JP31 pins 1 & 2 for nonresettable power (as illustrated
in figure to right)

Jumper JP31 pins 2 & 3 for resettable power

-
+
-
+

ms-10UDtb9.cdr

4
3
2
1

Figure 2.11 Relay Terminals

Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or total
power failure.