FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Introduction

Overview

Table 1.1 Reference Documentation

1.2 Overview

Communication between the control panel and intelligent addressable monitor and control devices
takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of
NFPA Style 4, Style 6, or Style 7.

At least one secondary surge protector must be used with each SLC wiring pair whenever SLC
wiring runs outside the building. For detailed information refer to “Surge Suppression” on page 64.

1.3 Polling Protocols

The MS-9200UDLS, MS-9600LS, and MS-9600UDLS support LiteSpeed protocol or Classic
Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E, and MS-9050UD
support Classic Loop Interface Protocol (CLIP) only.

1.3.1 Available Protocols

LiteSpeed is a communication protocol that greatly enhances the speed of communication between
analog intelligent devices. Only the MS-9200UDLS, MS-9600LS, and MS-9600UDLS are capable
of operating in LiteSpeed mode. This is the default mode of operation for these FACPs.

CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-LiteFireWarden
addressable fire alarm control panels can operate in CLIP mode. This is the default mode of
operation for all other FACPs.

1.3.2 Protocol Use

Use one of the following options with LiteSpeed/CLIP mode:

1. Program all modules and detectors on an FACP as LiteSpeed.
2. Program all modules and detectors on an FACP as CLIP.

When switching between polling protocols, the loop circuit must be powered down for at least 30
seconds to reset the devices.

BEAM355(S) Addressable Beam Detector

Installation Instructions

I56-2425

B210LP Plug-in Detector Base

Installation Instructions

I56-3739

B501 Detector Base

Installation Instructions

I56-0357 / I56-3738

B501BH Sounder Detector Base

Installation Instructions

I56-0491

B501BH-2 Sounder Detector Base

Installation Instructions

I56-2813

B501BHT Temporal Sounder Detector Base

Installation Instructions

I56-1367

B501BHT-2 Temporal Sounder Detector Base

Installation Instructions

I56-2819

B200SR Sounder Detector Base

Installation Instructions

I56-3387

B224RB Relay Detector Base

Installation Instructions

I56-2815 / I56-3737

B224BI Isolator Detector Base

Installation Instructions

I56-0725 / I56-3736

For information on...

Refer to...

Part Number

NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP
mode of operation. Communication protocols cannot be split between SLC loops.