3 mmf-300 wiring diagrams, 1 wiring a nfpa style b idc with an mmf-300, Mmf-300 wiring diagrams – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 34: Wiring a nfpa style b idc with an mmf-300

Advertising
background image

34

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Monitor Modules

MMF-300 Wiring Diagrams

5.3 MMF-300 Wiring Diagrams

Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating
Device Circuits (IDCs) using MMF-300 monitor modules.

The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamperes @ 24
VDC (nominal).

5.3.1 Wiring a NFPA Style B IDC with an MMF-300

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).

Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.

The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MMF-300 module.

Refer to the Device Compatibility Document for compatible smoke detectors.

See “Power Considerations” on page 61 for information on supervising 24 VDC power.

47K ELR
(supplied
with module)

Heat
detector

SLC

MMF-300

IDC

24 VDC Power
Filtered, Regulated,
Resettable

24 VDC
Four-wire
Detector Base

Manual pull
station

From Supply

To Next IDC
or
Supervision Device

S

L

C-id

cB

1tpH

.w

mf

Figure 5.9 Typical Style B IDC Wiring with an MMF-300

Advertising