Shield Wire Termination

Wiring Requirements

2.3 Shield Wire Termination

The drawing below shows the method of proper termination of the shield.

Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire
through the conduit, into the control box. The shield drain wire must be connected to the “shield”
terminal on the SLC terminal block.

NOTE: Use of good wiring practice consistent with local electrical codes is expected.

!

CAUTION:

DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE

SYSTEM CABINET OR BE CONNECTED TO EARTH GROUND AT ANY POINT.

Cabinet

SL

C-

sh

ie

ld

te

rm

.w

m

f

Shield Drain Wire

Shield Foil

Conduit

MS-9600
MS-9600LS
MS-9600UDLS
MS-9200UD
MS-9200UDLS
MS-9050UD

MS-9200

Figure 2.5 Shield Termination