62

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Power Considerations

Supervising 24 VDC Power

A.2 Supervising 24 VDC Power

Power used to supply 24 VDC detectors, notification appliances (using the CMF-300), and two
wire detectors (using the MMF-302) can be supervised with a power supervision relay. This relay,
energized by the 24 VDC power itself, is installed at the end of each respective power run and
wired in-line with the supervised circuit of any intelligent module.

24 VDC power must be provided from a UL-listed power supply for fire protection use.

When power is removed from the relay, the normally closed contacts open the supervised circuit,
generating a trouble condition. Therefore, the relay needs to be installed at the end of the super-
vised circuit, so it will not disrupt the operating capability of all the devices on that circuit. The
relay can be installed in-line with any leg (+ or –) of the supervised NAC circuit, either a Style B
(Class B) or a Style D (Class A) circuit.

The drawing below illustrates this concept.

S

L

C

-p

sr

tp

H

.c

d

r

24 VDC Power from
Control Panel or
Power Supply

Power Supervision

Relay

(EOLR-1)

Supervised NAC

ELR

47K

Last device on the SLC loop

Figure A.1 Supervised 24 VDC Circuit