FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Monitor Modules

MMF-300 Wiring Diagrams

5.3.3 MMF-300 Wiring for Emergency Alarm System Applications

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).

Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.

The figure below shows typical wiring for a supervised and power-limited Emergency Signaling
circuit using an MMF-300 module.

See “Power Considerations” on page 61 for information on supervising 24 VDC power.

See Section 6, “Control Modules” for instructions on using control modules as NACs on an
SLC.

For compatible output devices refer to the Device Compatibility Document #15384.

+

+

-

-

47K ELR

(supplied

with module)

SLC

MMF-300 Module

programmed for Tornado,

Hazard, or Medical operation.

Refer to the control panel

installation manual.

IDC

UL-listed Signaling
applicance such as the
Fire-Lite FSS-2400E

S

L

C

-em

er

.w

m

f

Figure 5.11 Emergency Signaling Wiring with an MMF-300