FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

54

Section 8: Multiple Input/Output Modules

8.1 Description

The CDRM-300 is an addressable module that functions as two individual relay control modules
(two isolated sets of Form-C relay contacts) and two Class B monitor modules.

Ratings for the relay contacts on the module are:

8.2 CDRM-300 Installation & Wiring

8.2.1 Setting an SLC address for a CDRM-300 Module

Each module is factory preset with an address of “00”. To set an SLC address, use a screwdriver to
adjust the rotary switches on the module to the desired address. Each module can use up to four (4)
addresses. The base address selected via the rotary address switches will be assigned to relay output
#1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to
monitored input #1, relay output #2, and monitored input #2.

Load Description

Application

Maximum

Voltage

Current

Rating

Inductive (PF = 0.35)

Non-Coded

25 VAC

2.0 A

Resistive

Non-Coded

30 VDC

3.0 A

Resistive

Coded

30 VDC

2.0 A

Inductive (L/R = 20ms)

Non-Coded

30 VDC

0.46 A

Inductive (PF = 0.35)

Non-Coded

70.7 VAC

0.7 A

Resistive

Non-Coded

125 VDC

0.9 A

Inductive (PF = 0.75)

Non-Coded

125 VAC

0.5 A

Inductive (PF = 0.35)

Non-Coded

125 VAC

0.3 A

NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.