2 wiring a nfpa style d idc with an mmf-300-10, Wiring a nfpa style d idc with an mmf-300-10 – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 38

Advertising
background image

38

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Monitor Modules

MMF-300-10 Wiring Diagrams

5.4.2 Wiring a NFPA Style D IDC with an MMF-300-10

Connect the SLC wiring to the module terminals T5 as shown below.

Use the rotary switches on the module to set the base SLC address. Each module takes five alternat-
ing addresses on the SLC. The remaining module points are automatically assigned to the next four
higher addresses. (Example: 28, 30, 32, 34 and 36). Refer to “Setting an SLC address for a Multi-
Point Module” on page 33.

DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.

The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-300-10 module.

Refer to the Device Compatibility Document for compatible smoke detectors.

See “Power Considerations” on page 61 for information on supervising 24 VDC power.

24 VDC Power
Filtered, Regulated, Resettable

24 VDC Four-wire
Detector Base

Manual Pull

Station

Heat

Detector

IDC
Out

MMF-300-10

SLC

IDC

Return

SL

C

-idcD3

.cdwmf

Figure 5.13 Typical Style D IDC Wiring with an MMF-300-10