FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Wiring Requirements

Measuring Resistance & Length

2.2.2 Four-Wire SLC Style 6 & 7 (Class A)

Loop Resistance

The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as detailed
and shown below.

1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the two leads of SLC channel A (Return).
3. Measure the resistance across the SLC channel B (Out) leads.

Total Wire Length

The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s
instruction manual. The figure below identifies the output and return loops from SLC terminal on
the control panel:

SLC

-m

eas3

.w

m

f

SLC Out

SLC Return

Short Point

Figure 2.3 Measuring DC Resistance of a Four-Wire SLC

B+ B– A– A+

SL

C

-m

eas4.

wm

f

SLC channel B
(output loop)

SLC channel A

(return loop)

SLC Terminal
Block

Figure 2.4 Measuring the Wire Length – Four-Wire SLC